Top
One stop solutions for Submersible Pump Cables

Drinking Water Submersible Pump Cable: Round

A flexible electric cable, with special rubber insulation and outer sheath, suitable for permanent immersion in drinking water. The cables have successfully passed rigorous testing of drinking water requirements of the British WRAS certification (according to BS 6920), the French ACS certification, the German KTW and W270 for direct and permanent immersion in potable water. The certification agencies have verified the absence of microbial growth, the water taste, appearance, transparency and colour and the absence of any metals or toxic substances.

Construction

Conductor

High purity electrolytic grade bright annealed flexible bunched bare, copper conductor according to international standards like IS 8130, BS 6360, IEC 228 & VDE 0295

Insulation

Oil & Water Resistant Thermoplastic Rubber Compound (TPE/TPR)

Sheath

Heavy Duty Thermoplastic Rubber Compound (TPE/TPR).

Standards

BS 6007, IEC 60245, CEI 20-19, VDE 0282, AS 3191, AS/NZS 5000.1, HD 22.1, , NF C 32-201, French Standard 32-102-16

Working Voltage Uo/U

450/ 750 V, 600/ 1000 V, 650/1100 V

Test Voltage

2500 V

Temperature range

-400C to 900C

Core colors (For Asian, African Markets) (For European Markets)
3 core Red ,Yellow, Blue Black, Blue, Brown
4 core Red ,Yellow, Blue, Green Black, Blue, Brown, Green
Sheath color: Choice of Black or Blue Choice of Black or Blue

Rubber 3 Core Double Sheathed Round Submersible Pump Cable

Area (nom)



sq.mm
No./size of wire


no./mm
Insulation thickness (nom.)

mm
Sheath thickness (nom.)

mm
Overall dimensions (approx.)

Mm
Conductor resistance at 200C (max.)

ohm /km
Current carrying capacity at 400C
amps.
3 x 1.5 22/.3 0.6 1.6 9.7 12.1 14
3 x 2.5 36/.3 0.7 1.6 10.7 7.41 18
3 x 4 56/.3 0.8 1.8 12.8 4.95 26
3 x 6 84/.3 0.8 1.8 14.4 3.3 31
3 x 10 140/.3 1 1.8 17.4 1.91 42
3 x 16 226/.3 1 2 21.2 1.21 57
3 x 25 354/.3 1.2 2.4 25.4 0.78 72
3 x 35 495/.3 1.2 2.6 29.1 0.554 90
3 x 50 703/.3 1.4 3.1 33.5 0.386 115
3 x 70 360/.5 1.4 3.1 39.1 0.272 143
3 x 95 475/.5 1.6 3.5 45.2 0.206 165

Rubber 4 Core Double Sheathed Round Submersible Pump Cable

Area (nom)



sq.mm
No./size of wire


no./mm
Insulation thickness (nom.)

mm
Sheath thickness (nom.)

mm
Overall dimensions (approx.)

Mm
Conductor resistance at 200C (max.)

ohm/km
Current carrying capacity at 400C
amps.
4 x 1.5 22/.3 0.6 1.6 10.5 12.1 14
4 x 2.5 36/.3 0.7 1.6 11.7 7.41 18
4 x 4 56/.3 0.8 1.8 14 4.95 26
4 x 6 84/.3 0.8 1.8 15.7 3.3 31
4 x 10 140/.3 1 1.8 19.1 1.91 42
4 x 16 226/.3 1 2 22.7 1.21 57
4 x 25 354/.3 1.2 2.6 29.4 0.78 72
4 x 35 495/.3 1.2 2.6 31.6 0.554 90
4 x 50 703/.3 1.4 3.1 37 0.386 115
4 x 70 360/.5 1.4 3.1 43.2 0.272 143
4 x 95 475/.5 1.6 3.5 50 0.206 165

Note:

Insulation thickness, Sheath thickness and overall dimensions are nominal values. The number of wires is approximate and strand diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance as per IS 8130/1984, BS-6360, IEC-60228 & VDE-0295.